Rating

1000 VA

1500 VA

2200 VA

Part number

05146630-5591

05146633-5591

05146637-5591

Capacity (VA/watts)

1000/700

1500/1050

2200/1600

Dimensions WxDxH (mm)

162x401x250

162x467x250

205x493x250

Weight (kg)

16

23

31

Input connection

IEC320/ 10A

Output connection

6xIEC320 10A

9xIEC320 10A

Typical runtime (Full load) pf 0,9

5 min

6 min

6 min

Typical runtime (Half load)

15 min

20 min

20 min

Operational
Nominal input voltage (Vac)

220/230/240 Vac

Input voltage range

166-276 VAC (+20/-30% of nominal)

Operating frequency

50/60 Hz auto sensing

Input power factor

Same as load

Nominal output voltage

220/230/240 Vac

Output voltage regulation

-10%/+6% of selected nominal voltage

Overload capacity

110% 3 min; 150% 10 cycles

Efficiency

95%

User interface
LED

Informative LED display

Standard communication ports

RS232

Optional

SNMP/WEB card, USB card

Environmental

Operating Temperature

0°C to +40°C

Storage Temp

-15°C to +55°C

Altitude

< 3000 M

Audible Noise

< 45 dB normal mode

<50 dB battery mode

Certification

Markings

CE/GS/UL

Safety

EN 50091-1-1 & UL 1778

EN 50091-2, EN6100-3-2

Battery cabinets

Battery cabinets

PW5125 24 V EBM for PW5125 1000 VA

PW5125 48 V EBM for PW5125 1500/2200 VA

Powerware 5125 Battery Run Time Chart (in minutes)
Load VA/W

1000 VA

1500 VA

2200 VA

250/175

30 (180)

60 (240)

100 (360)

500/350

15 (100)

35 (150)

60 (180)

750/525

10 (60)

20 (100)

45 (115)

1000/700

5 (48)

13 (60)

28 (75)

1250/875

8 (40)

19 (55)

1500/1050

6 (30)

15 (40)

1750/1225

12 (35)

2000/1400

10 (30)

2200/1600

6 (28)

* Run time chart provides typical information. Run times are approximate and may vary with equipment, configuration, battery age, temp. etc.