Powerware 5125 | |||||
Rating | 1000 VA | 1500 VA | 2200 VA | ||
Part number | 05146630-5591 | 05146633-5591 | 05146637-5591 | ||
Capacity (VA/watts) | 1000/700 | 1500/1050 | 2200/1600 | ||
Dimensions WxDxH (mm) | 162x401x250 | 162x467x250 | 205x493x250 | ||
Weight (kg) | 16 | 23 | 31 | ||
Input connection | IEC320/ 10A | ||||
Output connection | 6xIEC320 10A | 9xIEC320 10A | |||
Typical runtime (Full load) pf 0,9 | 5 min | 6 min | 6 min | ||
Typical runtime (Half load) | 15 min | 20 min | 20 min | ||
Operational | |||||
Nominal input voltage (Vac) | 220/230/240 Vac | ||||
Input voltage range | 166-276 VAC (+20/-30% of nominal) | ||||
Operating frequency | 50/60 Hz auto sensing | ||||
Input power factor | Same as load | ||||
Nominal output voltage | 220/230/240 Vac | ||||
Output voltage regulation | -10%/+6% of selected nominal voltage | ||||
Overload capacity | 110% 3 min; 150% 10 cycles | ||||
Efficiency | 95% | ||||
User interface | |||||
LED | Informative LED display | ||||
Standard communication ports | RS232 | ||||
Optional | SNMP/WEB card, USB card | ||||
Environmental | |||||
Operating Temperature | 0°C to +40°C | ||||
Storage Temp | -15°C to +55°C | ||||
Altitude | < 3000 M | ||||
Audible Noise | < 45 dB normal mode | ||||
<50 dB battery mode | |||||
Certification | |||||
Markings | CE/GS/UL | ||||
Safety | EN 50091-1-1 & UL 1778 | ||||
EN 50091-2, EN6100-3-2 | |||||
Battery cabinets | |||||
Battery cabinets | PW5125 24 V EBM for PW5125 1000 VA | ||||
PW5125 48 V EBM for PW5125 1500/2200 VA | |||||
Powerware 5125 Battery Run Time Chart (in minutes) | |||||
Load VA/W | 1000 VA | 1500 VA | 2200 VA | ||
250/175 | 30 (180) | 60 (240) | 100 (360) | ||
500/350 | 15 (100) | 35 (150) | 60 (180) | ||
750/525 | 10 (60) | 20 (100) | 45 (115) | ||
1000/700 | 5 (48) | 13 (60) | 28 (75) | ||
1250/875 | 8 (40) | 19 (55) | |||
1500/1050 | 6 (30) | 15 (40) | |||
1750/1225 | 12 (35) | ||||
2000/1400 | 10 (30) | ||||
2200/1600 | 6 (28) | ||||
* Run time chart provides typical information. Run times are approximate and may vary with equipment, configuration, battery age, temp. etc. | |||||